short circuit current rating
AA
Alon Avivi
Feb-9th, 2020 10:31

Unistronics VFD has built In short circuit current rating according to the following table:

  • B1-UL series (models <4kW) the rating is 5kA.
  • B5-UL series:
    • 3ph 208VAC 0.7kW-55kW, 10kA.
    • 3ph 460VAC 1.5kW-18kW, 5kA.
    • 3ph 460VAC 22W-110kW, 10kA.

 

SCCR = ISC (sometimes used ISC instead of SCCR)

Was this article helpful?
2 out of 2 found this helpful
 

 Unitronics VFDs

  • Unitronics UMI Workshop
  • VisiLogic and VFD
  • UMI (Unitronics VFD) Regenerative
  • UMI (Unitronics VFD) Heat Dissipation
  • Cable length between VFD and motor
  • VFD - Configuring 2 frequency sources
  • UMI Braking Resistor Calculation
  • UMI (Unitronics VFD)
  • VFD Keypad Password
  • VFD - Stop VFD when communication lost with PLC
  • Unitronics VFD Quick Start Guide
  • Unitronics Motion Inverter cable gauge and required Torque for Terminals
  • Unitronics VFD UMI Short Current Ratings and recommended protection devices
  • Unitronics VFDs B1 series Dimensions
  • Unitronics VFDs B5 series Dimensions
  • VFD-Multi-set speed
  • Filter installation and dimensions in Inverter
  • Connecting multiple motors to a single VFD
  • Running VFD frequency via Modbus and control via Terminal.
  • UMI-B1- STO Functional Safety Data
  • Auto start for VFD
  • short circuit current rating
  • UMI VFD Integration on BACNET IP network

Help Desk Software by Vision Helpdesk